Plan View - Front Opening Only

Capacity  Ibs [kg] 2500  [1134] 3000  [1360] 3500  [1588] 4000  [1814]
Door Size 3'-6"  [1067] 3'-6"  [1067] 3'-6"  [1067] 4'-0"  [1219]
System 1SCO 1SCO 1SCO 1SCO
Platform Size
Width
Depth
 
7'-0"  [2134]
5'-0 ½"  [1537]
 
7'-0"  [2134]
5'-6 ½"  [1689]
 
7'-0"  [2134]
6'-2 ½"  [1892]
 
8'-0"  [2438]
6'-2 ½"  [1892]
Clear Inside Applied Panels
Width
Depth
 
6'-8"  [2032]
4'-3"  [1295]
 
6'-8"  [2032]
4'-9"  [1448]
 
6'-8"  [2032]
5'-5"  [1651]
 
7'-8"  [2337]
5'-5"  [1651]
Clear Inside Steel Shell
Width
Depth
 
6'-9 ½"  [2070]
4'-3 ¾"  [1314]
 
6'-9 ½"  [2070]
4'-9 ¾"  [1467]
 
6'-9 ½"  [2070]
5'-5 ¾"  [1670]
 
7'-9 ½"  [2375]
5'-5 ¾"  [1670]
Hoistway Clear Width 8'-4"  [2540] 8'-4"  [2540] 8'-4"  [2540] 9'-4"  [2845]
Hoistway Clear Depth 6'-8"  [2032] 7'-2"  [2184] 7'-10"  [2387] 7'-10"  [2387]

 

Plan View - Front & Rear Openings

Capacity  Ibs [kg] 2500  [1134] 3000  [1360] 3500  [1588] 4000  [1814]
Door Size 3'-6"  [1067] 3'-6"  [1067] 3'-6"  [1067] 4'-0"  [1219]
System 1SCO 1SCO 1SCO 2SCO
Platform Size
Width
Depth
 
7'-0"  [2134]
5'-6 ¾"  [1695]
 
7'-0"  [2134]
6'-0 ¾"  [1848]
 
7'-0"  [2134]
6'-8 ¾"  [2051]
 
8'-0"  [2438]
6'-8 ¾"  [2051]
Clear Inside Applied Panels
Width
Depth
 
6'-8"  [2032]
4'-3 ¾"  [1314]
 
6'-8"  [2032]
4'-9 ¾"  [1467]
 
6'-8"  [2032]
5'-5 ¾"  [1670]
 
7'-8"  [2337]
5'-5 ¾"  [1670]
Clear Inside Steel Shell
Width
Depth
 
6'-9 ½"  [2070]
4'-3 ¾"  [1314]
 
6'-9 ½"  [2070]
4'-9 ¾"  [1467]
 
6'-9 ½"  [2070]
5'-5 ¾"  [1670]
 
7'-9 ½"  [2375]
5'-5 ¾"  [1670]
Hoistway Clear Width  9'-6"  [2896] 9'-6"  [2896] 9'-6"  [2896] 10'-6"  [3200]
Hoistway Clear Depth 6'-7 ¼"  [2013] 7'-1 ¼"  [2165] 7'-9 ¼"  [2369] 7'-9 ¼"  [2369]

 

Section View - All

Speed
fpm [mps]
Pit Depth
(Min)
P
 
 
8'-0" Cab
Overhead
OH
9'-0" Cab
 
 
10'-0" Cab
350  [1.75] 5'-6"  [1676] 14'-2"  [4318] 15'-2"  [4623] 16'-2"  [4928]
500  [2.5] 6'-8"  [2032] 15'-3"  [4648] 16'-3"  [4953] 17'-3"  [5258]

Notes:

1) If seismic zone, add 2in [51mm] to hoistway depth.
2) If occupied space below, add 5in [127mm] to hoistway depth for CWT safety.
3) If both seismic and occupied below, add 6½in [165mm] to hoistway depth.
4) If vertical travel exceeds 300ft [90m], add 2in [51mm] to hoistway width.
5) Overhead dimension is from top landing to underside of machine beams.
6) Dimensions may vary for specific applications - Consult your Fujitec sales
     representative for final confirmation of details.